HospitalityExtinguisher Rules for Employers
Twenty flashcards on the federal rule for portable fire extinguishers at work: exemptions, placement, inspection and training.
Free to start20 cards
- What does the federal portable extinguisher rule cover?
- Placement, use, maintenance and testing of portable extinguishers provided for employees.
- Extinguishers are there but not for employee use, with an emergency action plan and fire prevention plan. What applies?
- Only the inspection, maintenance and testing paragraphs and the hydrostatic testing paragraphs.
- When is the employer exempt from the whole rule?
- With a written policy of immediate, total evacuation at the fire alarm, an emergency action plan and fire prevention plan, and no extinguishers in the workplace.
- Only designated employees may use extinguishers and everyone else evacuates. Which part is waived?
- The distribution requirements.
- How must extinguishers be mounted and located?
- Readily accessible to employees, without exposing them to possible injury.
- Which extinguishers may be used to meet the rule?
- Only approved portable fire extinguishers.
- Which extinguishing agents are banned at work?
- Carbon tetrachloride and chlorobromomethane.
- In what condition must extinguishers be kept?
- Fully charged, operable and in their designated places at all times, except during use.
- Maximum travel distance to an extinguisher for Class A fires?
- 75 feet (22.9 m) or less.
- Maximum travel distance from a Class B hazard to an extinguisher?
- 50 feet (15.2 m) or less.
- Maximum travel distance from a combustible metal area to Class D agent?
- 75 feet (22.9 m) or less.
- Who is responsible for inspecting, maintaining and testing extinguishers?
- The employer, for all portable extinguishers in the workplace.
- How often must portable extinguishers be visually inspected?
- Monthly.
- How often is the maintenance check, and how long is it recorded?
- Annually; the date is kept for one year after the last entry or the life of the shell, whichever is less.
- Stored pressure dry chemical extinguishers needing a 12-year hydrostatic test: what else?
- They are emptied and given maintenance every 6 years.
- What must the employer provide while extinguishers are out for maintenance?
- Alternate equivalent protection.
- Hydrostatic test interval for carbon dioxide extinguishers in the federal table?
- 5 years.
- What education is owed when extinguishers are provided for employees?
- A program on the general principles of extinguisher use and the hazards of incipient stage fire fighting, at hire and at least annually.
- What extra training do designated extinguisher users get?
- Training on the right equipment, when first assigned and at least annually.
- What are the four fire options an employer can choose?
- Total evacuation; only designated employees fight; all employees fight; extinguishers provided but not for employee use.