Twenty flashcards on the federal fire prevention plan and on the employee alarm that warns everyone to get out.

Free to start
Your progress here is temporary and is lost when you close this page. Install Making Synapses free to keep it, with spaced repetition.

20 cards
When must an employer have a fire prevention plan?
When an OSHA standard in that part of the rules requires one.
Must the fire prevention plan be written?
Yes: written, kept at the workplace and available to employees; with 10 or fewer employees it may be told orally.
What is the purpose of a fire prevention plan?
To prevent a fire from happening in the workplace.
What does a fire prevention plan describe?
The fuel sources that could start or spread a fire, and the building systems, like fixed extinguishing and alarms, that control it.
Fire prevention plan element 1?
A list of major fire hazards, safe handling and storage of hazardous materials, ignition sources and their control, and the fire equipment for each hazard.
Fire prevention plan element 2?
Procedures to control buildups of flammable and combustible waste.
Fire prevention plan element 3?
Regular maintenance of safeguards on heat-producing equipment, so it cannot accidentally ignite materials.
Fire prevention plan element 4?
The name or job title of those who maintain equipment that prevents or controls ignition sources or fires.
Fire prevention plan element 5?
The name or job title of those responsible for controlling fuel source hazards.
What must each employee hear on first assignment?
The fire hazards they are exposed to, and the parts of the plan they need to protect themselves.
Who must be able to perceive the employee alarm?
All employees in the affected areas, above ambient noise or light; tactile devices can help those who cannot hear or see it.
What is the standard audible evacuation signal?
A three-pulse pattern: three 0.5 second tones with 0.5 second gaps, then 1.5 seconds off, for a 4.0 seconds cycle.
When is the three-pulse signal used?
Only to call for immediate evacuation of the building; relocation or shelter in place needs a different signal.
How loud and bright should alarms be?
Audible alarms at least six decibels over ambient noise; visual alarms at least 75 candela.
Why limit strobe flashing to five flashes per second?
Faster rates can trigger seizures in people with certain forms of epilepsy.
At what height are alarm devices mounted?
80 inches above the highest floor level or six inches below the ceiling, whichever is lower.
How often are non-supervised alarm systems tested?
Every two months, using a different activation device each time.
Is a voice alarm enough in a small workplace?
With 10 or fewer employees, direct voice works if everyone can hear it, with no back-up needed.
How must manual pull stations be kept?
Unobstructed, conspicuous and readily accessible.
Where should visual alarms go?
At least one in each room and general use area, such as guest restrooms and meeting rooms.

Official sources

Occupational Safety and Health Administration (OSHA), via GovInfo (GPO)

29 CFR 1910.39: Fire prevention plans (CFR 2025 edition)